Sobre Nexans
Productos y Soluciones
Servicios al cliente
Trabaje en Nexans
Noticias y prensa
Construction
24 AWG bare copper wire insulated with polyethylene (non-plenum). Two layer core construction jacketed in flame-retardant PVC (non-plenum).
Standards
Flame Rating
Benefits
Technical Data - Physical
Color Code
See Below
Conductor
24 AWG Bare Copper
Conductor diameter–in. (mm)
0.021
(0.53)
Insulated Conductor Diameter- in. (mm)
0.038
(0.97)
Cable diameter–in. (mm)
0.5
(11.6)
Nominal cable weight–lb./kft. (kg/km)
132
(210)
Temperature Rating
Max. installation tension–lb. (N)
25
(110)
Installation
0°C to +50°C
Min. bend radius–in. (mm)
5
(127)
Operation
-20°C to +75°C
Pair 1
White
Blue
Pair 13
Black
Green
Pair 2
Orange
Pair 14
Brown
Pair 3
Pair 15
Gray
Pair 4
Pair 16
Yellow
Pair 5
Pair 17
Pair 6
Red
Pair 18
Pair 7
Pair 19
Pair 8
Pair 20
Pair 9
Pair 21
Violet
Pair 10
Pair 22
Pair 11
Pair 23
Pair 12
Pair 24
Pair 25
Mutual Capacitance
5.6 nF/100 m nom. @ 1 KHz
DC resistance
9.38 Ohms/100 m max.
Skew
45 ns/100 m max.
Pair to ground Unbalance
330 pF/100 m max.
Velocity of Propagation
72% nom.
Input Impedance
100 ± 15% 0.772-100 MHz
DC Resistance Unbalance:
5% max.
FREQUENCY(MHz)
Insertion Loss(dB/100 m max.)
RL(dB min.)
SRL(dB min.)
PS-NEXT(dB min.)
NEXT(dB min.)
ELFEXT (dB min.)
PS-ELFEXT(dB min.)
1
2
20
62.3
65.3
63.8
60.8
4
4.1
23
53.2
56.3
51.7
48.7
10
6.5
47.3
50.3
43.8
40.8
16
8.2
44.2
39.7
36.7
9.3
42.7
45.8
37.7
34.7
31.25
11.7
23.6
39.8
42.9
33.9
30.9
62.5
17
21.5
35.3
38.4
27.8
24.8
100
22
20.1
32.3
23.8
20.8
150
27.5
18.9
29.7
32.7
20.2
17.2
200
32.4
18.0
30.8
17.7
14.7
250
36.9
17.3
26.3
29.3
15.8
12.8