About Nexans
Products and Solutions
Customer Service
Work at Nexans
News and Press
Construction
24 AWG) bare copper wire insulated with thermoplastic. Three layer core construction jacketed in flame retardant PVC.
Standards
Flame Rating
Applications
Berk-Tek's Multi-Pair Category 3 UTP Power Sum Backbone cables are intended for data and voice applications including:
Features
Benefits
Frequency(MHz)
Insertion Loss(dB/100m max)
SRL(dB min)
PS-NEXT(dB min)
1
2.6
12
41.3
4
5.6
32.3
10
9.8
26.3
16
13.1
23.3
25 PR(CMR)
25 PR(CMP)
50 PR(CMR)
50 PR(CMP)
100 PR(CMR)
Mutual Capacitance, nF/100 m nom.
6.6
DC Resistance, Ohms/100 m max.
9.4
Conductor diameter—in. (mm)
0.02(0.51)
Cable diameter—in. (mm)
.390(9.9)
.382(9.7)
.525(13.3)
.496(12.59)
.895(22.72)
Nominal cable weight lb/k ft.(kg/km)
97(144)
100(148)
196(290)
198(293)
387(573)
100 PR(CMP)
200 PR(CMR)
200 PR(CMP)
300 PR(CMR)
300 PR(CMP)
.889(22.57)
1.123(28.51)
1.012(25.69)
1.314(33.36)
1.27(32.25)
Nominal cable weight lb/k ft. (kg/km)
395(585)
691(1023)
1226(1814)
Pair 1
White/Blue
Blue/White
Pair 13
Black/Green
Green/Black
Pair 2
White/Orange
Orange/White
Pair 14
Black/Brown
Brown/Black
Pair 3
White/Green
Green/White
Pair 15
Black/Gray
Gray/Black
Pair 4
White/Brown
Brown/White
Pair 16
Yellow/Blue
Blue/Yellow
Pair 5
White/Gray
Gray/White
Pair 17
Yellow/Orange
Orange/Yellow
Pair 6
Red/Blue
Blue/Red
Pair 18
Yellow/Green
Green/Yellow
Pair 7
Red/Orange
Orange/Red
Pair 19
Yellow/Brown
Brown/Yellow
Pair 8
Red/Green
Green/Red
Pair 20
Yellow/Gray
Gray/Yellow
Pair 9
Red/Brown
Brown/Red
Pair 21
Violet/Blue
Blue/Violet
Pair 10
Red/Gray
Gray/Red
Pair 22
Violet/Orange
Orange/Violet
Pair 11
Black/Blue
Blue/Black
Pair 23
Violet/Green
Green/Violet
Pair 12
Black/Orange
Orange/Black
Pair 24
Violet/Brown
Brown/Violet
Pair 25
Violet/Gray
Gray/Violet
Application note: If installing as 6 4-pr. connections, use sequential pairs (1-4, 5-8, etc.) to ensure standard performance
Installation
0°C to +50°C
Operation
-10°C to +60°C