XLPE insulated MV overhead lines

Send link to this page print Your Nexans contact on this page
XLPE insulated MV overhead lines XLPE-insulated overhead cables
Standards
National  DIN VDE 0276 part 620 adapted
Description

Construction

single core: stranded aluminium conductor - conductor screen of semiconducting compound - insulation of cross-linked polyethylene (XLPE) - screen of semiconducting compound - semiconducting bedding plus copper wires and copper tape - separation tape - PE sheath

supporting strand: Conductor of stranded Aldrey wires - PE sheath

Overhead cable: Three single cores laid-up over the supporting strand

 

Application

Outdoors, in ground, indoors and in cable ducts

Conditions for current load

ambient temperature         35°C

wind velocity                      0.6m/s

load factor                        1.0

direct exposures to sunlight

conductor temperature under

standard load                    90°C

conductor temperature under

short circuit conditions         250°C


 TOP
Characteristics
Construction characteristics
Conductor material Aluminium  
Conductor shape Circular stranded (RM)  
Material of the inner semi-conductor Compound  
Insulation XLPE (chemical)  
Material of the external semi-conductor Compound  
Material of bedding Semiconducting  
Screen Copper wire + copper tape  
Protection separation tape  
Outer sheath PE  
Messenger PE sheathed conductor of stranded Aldrey wires  
Dimensional characteristics
Number of cores 3  
Screen section 16mm²  
Usage characteristics
Bending factor when laying 12(xD)  
Ambient temperature 35°C  
Minimum installation temperature -20°C  
Max. conductor temperature in service 90°C  
Short-circuit max. conductor temperature 250°C  

 TOP
Your selection
Average insulation thickness  mm
Average sheath thickness  mm
Nominal outer diameter  mm
Messenger cross-section  mm²
Messenger conductor diameter  mm
Messenger insulation thickness  mm
Overall messenger diameter  mm
Diameter over assembly  mm
Approximate weight  kg/km
Permissible current rating in open air  A
Apply
Reset
Results   6/6
Select all Items Nexans ref. Name Av. insul. thickness (mm) Average sheath thickness (mm) Nom. outer diam. (mm) Messenger cross-section (mm²) Messenger conduct. diam. (mm) Messenger insul. thickness (mm) Overall messenger diameter (mm) Diameter over assembly (mm) Approx. weight (kg/km) Perm. current rating open air (A)
Make to order product 2... A2XS2YT 3x1x50RM/16 6/10 kV 3.4 2.5 27.0 70 10.5 1 12.5 66.0 2310 174
Make to order product 2... A2XS2YT 3x1x70RM/16 6/10 kV 3.4 2.5 28.0 70 10.5 1 12.5 69.0 2600 217
Make to order product 2... A2XS2YT 3x1x95RM/16 6/10 kV 3.4 2.5 30.0 70 10.5 1 12.5 72.0 2930 264
Make to order product 2... A2XS2YT 3x1x50RM/16 12/20 kV 5.5 2.5 31.0 70 10.5 1 12.5 74.0 2800 176
Make to order product 2... A2XS2YT 3x1x70RM/16 12/20 kV 5.5 2.5 32.0 70 10.5 1 12.5 77.0 3120 220
Make to order product 2... A2XS2YT 3x1x95RM/16 12/20 kV 5.5 2.5 34.0 70 10.5 1 12.5 81.0 3490 267
Add to favorites

 TOP
Selling delivery information
Note: When jointing insulated overhead cables to U.G. cables, the current carrying capacities according to DIN VDE 0276-620 must be taken into consideration. We shall be pleased to indicate the sag values upon request.