Application :New european test -known as AD8, specify from now on strictlier performance of the materials used in H07RN8-F cables. These cables are made for carriable machine like submergerd pump and for immersed pump too.They can be used in every submerged environment like ports, offshore rigs... The good resitance of sheathing material to oil, grease and chimical product allow various usage. Used in fixed installation they could be adapted for evacuation system H07RN8-F cables are made with specific synthetic rubber having high waterproof degree can be used for intensive applications. Use up to 1000V in alternative current is authorized for protected static installations and for connecting of motors in lifting appliances. Maximum temperature on conductor in normal use + 60°C and under short circuit condition 200°C. AD8 application Cenelec test 100 days.Submersible - 10 m.InstallationCan be used in open air. If buried it must have an extra mechanical protection (tube, gutter). Conductors laid up assembled conductor. Filler and reinforcement tape in some case. Tractive force Maxi 15N/mm² in relation to the section of core or 1000 N max for the full cable. MarkingUSE <HAR> H07RN8-F N X (or G) S- N = number of cores
- G = with Green/Yellow
- x = without Green/Yellow
- S = section in mm²
NotaMax continuous operating conductor temperature in normal use : +60°C ( in every case of mobile installation) +85°C ( fixed protected installation ) +200°C ( in short circuit ) Permissible current rating is measured for an ambient temperature of 30°C and a maximum operating and conductor temperature of 85°C . For other temperature please refer to correction factors .
|