MPRX® 331 0.6/1 (1.2) kV

Send link to this page print Your Nexans contact on this page
MPRX® 331 0.6/1 (1.2) kV INFIT Technology
This product is part of our Shiplink® offer
Standards
International  IEC 60092-350; IEC 60092-351; IEC 60092-353; IEC 60092-359; IEC 60228; IEC 60331-21 ; IEC 60332-3-22; IEC 60754-1; IEC 60754-2; IEC 61034
Description

Application

MPRX® 331 type is used on board of ships in all locations below the upper metallic deck for fixed installations complying with IEC standards 60092-352 and in safety circuits, where fire resistance is required.

MPRX® 331 type meets the IEC 60331-21 fire resistant performances, withstands the IEC 60332-3-22 fire test on bunched cables and performs to the SOLAS requirements.

Design

All materials used to produce this cable are halogen free. This design ensures that non corrosive and low toxic gases are emitted in case of fire. Therefore, this cable type is especially designed for installations on passenger ships. Insulation carried according to INFIT technology.

  1. Conductor:
    Bare copper
    Stranded class 2
  2. Insulation:
    • Cross section 1.5 - 2.5 - 4 mm²:
      Special Fire Resistant
      Halogen Free Compound
    • Cross section >/= 6mm²:
      Mica Tape + XLPE
      (cross linked polyethylene)
      (sector shaped >/= 70 mm² 3 cores)
  3. Outer sheath:
    (Filler if necessary)
    Polyolefin SHF1
    Colour: orange
    SHF2 on request

Type Approval Certificates


China Classification Society
Burea Veritas
Det Norske Veritas
Germanischer Lloyd
Lloyd's Register of Shipping
Registro Italiano navale


 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Conductor flexibility Stranded class 2  
Insulation XLPE + Mica tape  
Material of filler / inner sheath Filler if necessary  
Outer sheath Polyolefin  
Halogen free IEC 60754-1  
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/ 1 (1.2) kV  
Usage characteristics
Fire retardant IEC 60332-3-22  
Smoke density IEC 61034  
Gases toxicity No  
Gases corrosivity IEC 60754-2  
Max. conductor temperature in service 90°C  
Operating temperature, range -30 .. 80°C  
Fire resistant IEC 60331-21  
Standard IEC  

 TOP
Selling delivery information

Core identification

  • 1 core : black
  • 2 cores : brown - blue
  • 2 cores+E : brown - blue - green/yellow
  • 3 cores : black - grey - brown
  • 3 cores+E : black - grey - brown - green/yellow
  • 4 cores : black - grey - brown - blue
  • 4 cores+E : black - grey - brown - blue - green/yellow
  • from 5 cores and above: white with black printed numbers

Marking

NEXANS 205 MPRX 331* 0.6/1 kV "n" x (orG) "s" 90°C IEC 60332-3-22 "WW/YY" * CE* PF + Metric marking